Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 12, 2022, 05:31 AM
  • 16 0168_16 0167_08112022_223530.mp4

Date
08/11/2022
W/O
967378
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00648
PipeID
P13200
Time
10:31 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10322
Sewer Name
16 ARROYO SECO TRUNK, SECTION 5
City
SOUTH PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
17
Purpose
Routine Assessment
Project
RFIR_WO_967378_TV16081_AUG2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
16 in.
Width
16 in.
Upstream MH
16 0168
Downstream MH
16 0167
Dir. of Survey
Downstream
Length Surveyed
47.8 ft.
Total Length
47.8 ft.
Structural Index
2
Structural Quick
3329
Structural Rating
27
O&M Index
2
O&M Quick
2900
O&M Rating
18
Overall Index
2
Overall Quick
Overall Rating
45
Pipe schematic from manhole 16 0168 to 16 0167
MH: 16 0168MH: 16 0167downstream0 ft. AMH - Upstream Manhole, Survey Begins - 16 01680 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 10 %of cross sectional area2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start45 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish45 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish45.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish47.8 ft. AMH - Downstream Manhole, Survey Ends - 16 016747.8 ft. MGO - General Observation - ROACHES @ MH

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - ROACHES @ MH

    47.8 ft. - General Observation - ROACHES @ MH

Observations (11)

DistanceCodeObservation
0AMH16 0168
2CM
0MWL
2SSS
45DAGS
2DAGS
45SSS
47.8AMH16 0167
47.8MGOROACHES @ MH
0MWM
45.7CM

Properties (7)

additional_info
630098081122201
custom_field_three
CRACKS
custom_field_two
2
customer
1
datetime
2022-08-11T22:31:58-07:00
documentation
PRO PIPE
is_lateral_inspection
false