Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 16, 2022, 08:00 AM
  • 16 0163_16 0162_08162022_011733.mp4

Date
08/16/2022
W/O
967378
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00648
PipeID
P13195
Time
1:00 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10328
Sewer Name
16 ARROYO SECO TRUNK, SECTION 5
City
SOUTH PASADENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
20
Purpose
Routine Assessment
Project
RFIR_WO_967378_TV16081_AUG2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
16 0163
Downstream MH
16 0162
Dir. of Survey
Downstream
Length Surveyed
521.7 ft.
Total Length
521.7 ft.
Structural Index
3
Structural Quick
3T2T
Structural Rating
521
O&M Index
2
O&M Quick
2T00
O&M Rating
206
Overall Index
2
Overall Quick
Overall Rating
727
Pipe schematic from manhole 16 0163 to 16 0162
MH: 16 0163MH: 16 0162downstream0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 16 01630 ft. MWL - Water Level, 5 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start34.2 ft. H - Hole, at 09 o'clock, within 8 inches of joint: NO - ACTIVE34.2 ft. TBA - Tap Break-In Active, at 09 o'clock, -, within 8 inches of joint: YES, 4"87.7 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"145.3 ft. H - Hole, at 09 o'clock, within 8 inches of joint: NO - ACTIVE145.3 ft. TBA - Tap Break-In Active, at 09 o'clock, -, within 8 inches of joint: YES, 4"197.6 ft. TBA - Tap Break-In Active, at 09 o'clock, -, within 8 inches of joint: YES, 6", 6"266.7 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"326 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"374.7 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"444.9 ft. TBA - Tap Break-In Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"519 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish519 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish519.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish521.7 ft. AMH - Downstream Manhole, Survey Ends - 16 0162

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (20)

DistanceCodeObservation
2DAGS
2CM
87.7TBA
326TBA
2SSS
519.3CM
145.3HACTIVE
0MWM
34.2HACTIVE
197.6TBA
34.2TBA
519SSS
519DAGS
266.7TBA
145.3TBA
0AMH16 0163
0MWL
521.7AMH16 0162
444.9TBA
374.7TBA

Properties (7)

additional_info
630098081522203
custom_field_three
MULTIPLE BREAK IN ACTIVE HOLES/MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2022-08-16T01:00:12-07:00
documentation
PRO PIPE
is_lateral_inspection
false