Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 10, 2022, 10:52 AM
  • 05 1514_05 1513_08102022_040751.mp4

Date
08/10/2022
W/O
967330
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00528
PipeID
P06736
Time
3:52 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10274
Sewer Name
05 TORRANCE EXTENSION TRUNK
City
TORRANCE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
29
Purpose
Routine Assessment
Project
RFIR_WO_967330_TV05210_AUG2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
15 in.
Upstream MH
05 1514
Downstream MH
05 1513
Dir. of Survey
Downstream
Length Surveyed
360 ft.
Total Length
360 ft.
Structural Index
4
Structural Quick
4331
Structural Rating
15
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
3
Overall Quick
Overall Rating
16
Pipe schematic from manhole 05 1514 to 05 1513
MH: 05 1514MH: 05 1513downstream0 ft. AMH - Upstream Manhole, Survey Begins - 05 15140 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area3.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start119.3 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES162.1 ft. FM - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES165.8 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"216.2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES258.8 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"264.8 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"321.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES357.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish360 ft. AMH - Downstream Manhole, Survey Ends - 05 1513

Observation photos (6)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES

    119.3 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES

    162.1 ft. - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    216.2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    258.8 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    321.3 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (13)

DistanceCodeObservation
0AMH05 1514
119.3RFJ
216.2FM
357.6CM
0MWM
162.1FM
264.8TF
3.2CM
165.8TFC
0MWL
321.3FM
258.8TB
360AMH05 1513

Properties (7)

additional_info
630074080922203
custom_field_three
MULTIPLE CRACKS/FRACTURE'S
custom_field_two
2
customer
1
datetime
2022-08-10T03:52:53-07:00
documentation
PROPIPE
is_lateral_inspection
false