Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 17, 2022, 08:06 AM
  • 14 0306_14 0305A_08172022_011724.mp4

Date
08/17/2022
W/O
967355
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00583
PipeID
P20163
Time
1:06 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10332
Sewer Name
14 TRUNK "F"
City
LANCASTER
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
16
Purpose
Routine Assessment
Project
RFIR_WO_967355_TV14076_AUG2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
14 0306
Downstream MH
14 0305A
Dir. of Survey
Downstream
Length Surveyed
314 ft.
Total Length
314 ft.
Structural Index
3
Structural Quick
3J2J
Structural Rating
285
O&M Index
2
O&M Quick
2K00
O&M Rating
124
Overall Index
2
Overall Quick
Overall Rating
409
Pipe schematic from manhole 14 0306 to 14 0305A
MH: 14 0306MH: 14 0305Adownstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 14 03060 ft. MWL - Water Level, 15 %of cross sectional area2 ft. MGO - General Observation - 65% MAG COAT2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start26.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start26.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start310.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish310.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish311 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish314 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE314 ft. AMH - Downstream Manhole, Survey Ends - 14 0305A

Observation photos (2)

  • General Observation - 65% MAG COAT

    2 ft. - General Observation - 65% MAG COAT

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    26.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
0MWM
0AMH14 0306
26.1SAV
314MGOCONN @ MH 3 O'CLOCK/ACTIVE
311DAGS
314AMH14 0305A
0MWL
2MGO65% MAG COAT
2DAGS
310.9SSS
26.1SSS
310.9SAV

Properties (7)

additional_info
630098081622202
custom_field_three
SPALLING/VISIBLE AGGREGATE
custom_field_two
2
customer
1
datetime
2022-08-17T01:06:23-07:00
documentation
PRO PIPE
is_lateral_inspection
false