Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 4, 2022, 10:03 AM
  • 02 1036_02 0984_08042022_031821.mp4

Date
08/04/2022
W/O
967275
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00306
PipeID
P04592
Time
3:03 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10317
Sewer Name
02 TELEGRAPH ROAD TRUNK
City
COMMERCE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
21
Purpose
Routine Assessment
Project
WO_967275_TV02432_AUG2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
21 in.
Upstream MH
02 1036
Downstream MH
02 0984
Dir. of Survey
Downstream
Length Surveyed
220.9 ft.
Total Length
220.9 ft.
Structural Index
3
Structural Quick
3G12
Structural Rating
128
O&M Index
2
O&M Quick
412I
O&M Rating
108
Overall Index
2
Overall Quick
Overall Rating
236
Pipe schematic from manhole 02 1036 to 02 0984
MH: 02 1036MH: 02 0984downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 10360 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 40 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start8.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start23.5 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"98.6 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"175 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start - DEBRIS180.5 ft. JOM - Joint Offset Medium185.9 ft. JSM - Joint Separated Medium - / BROKEN / "CHIPPED" 8 TO 4 O'CLOCK.219.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish219.3 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish219.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish220.9 ft. AMH - Downstream Manhole, Survey Ends - 02 0984220.9 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK.

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    8.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Joint Offset Medium

    180.5 ft. - Joint Offset Medium

  • Joint Separated Medium - / BROKEN / "CHIPPED" 8 TO 4 O'CLOCK.

    185.9 ft. - Joint Separated Medium - / BROKEN / "CHIPPED" 8 TO 4 O'CLOCK.

Observations (15)

DistanceCodeObservation
98.6TFC
219.3CM
2DAGS
8.4CM
0AMH02 1036
220.9AMH02 0984
220.9MGOACTIVE CONNECTION AT MH 3 O'CLOCK.
219.3DSZ
0MWM
219.3DAGS
180.5JOM
23.5TFC
175DSZDEBRIS
185.9JSM/ BROKEN / "CHIPPED" 8 TO 4 O'CLOCK.
0MWL

Properties (7)

additional_info
630098080322207
custom_field_three
MULTIPLE CRACKS
custom_field_two
2
customer
1
datetime
2022-08-04T03:03:58-07:00
documentation
PRO PIPE
is_lateral_inspection
false