Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 1, 2022, 08:52 AM
  • 32 0249_32 0248_08012022_015820.mp4

Date
08/01/2022
W/O
962080
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00914
PipeID
P22499
Time
1:52 AM
Certificate
U-0720-70309212
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9999
Sewer Name
32 DISTRICT #32 MAIN RELIEF TRUNK
City
SANTA CLARITA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary
District
32
Page No.
08
Purpose
Routine Assessment
Project
RFIR_WO_962080_TV32056_JUL2022
Sewer Type
Siphon
Material
Vitrified Clay Pipe
Shape
Other
Height
36 in.
Upstream MH
32 0249
Downstream MH
32 0248
Dir. of Survey
Downstream
Length Surveyed
55.8 ft.
Total Length
55.8 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
4
Pipe schematic from manhole 32 0249 to 32 0248
MH: 32 0249MH: 32 0248downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 32 02490 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start35.6 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES55.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish55.8 ft. MSA - Survey Abandoned - VIEW OF DOWNLEG OF U/S SIPHON.

Observation photos (2)

  • Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

    35.6 ft. - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

  • Survey Abandoned - VIEW OF DOWNLEG OF U/S SIPHON.

    55.8 ft. - Survey Abandoned - VIEW OF DOWNLEG OF U/S SIPHON.

Observations (7)

DistanceCodeObservation
55.6DAGS
0MWL
0AMH32 0249
2DAGS
55.8MSAVIEW OF DOWNLEG OF U/S SIPHON.
35.6CL
0MWM

Properties (7)

additional_info
630074080122001
custom_field_three
CRACK
custom_field_two
3
customer
LACSD
datetime
2022-08-01T01:52:40-07:00
documentation
PRO PIPE
is_lateral_inspection
false