Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 4, 2022, 08:09 AM
  • 02 2255_02 1582_08042022_004935.mp4

Date
08/04/2022
W/O
967358
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00231
PipeID
P04034
Time
1:09 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10314
Sewer Name
02 ARIZONA AVENUE TRUNK, SECTION 2
City
EAST LOS ANGELES
Loc. details
Sidewalk
Location Code
F
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
08
Purpose
Routine Assessment
Project
RFIR_WO_967358_TV02431_AUG2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
15 in.
Upstream MH
02 2255
Downstream MH
02 1582
Dir. of Survey
Downstream
Length Surveyed
318.8 ft.
Total Length
318.8 ft.
Structural Index
3
Structural Quick
513K
Structural Rating
188
O&M Index
2
O&M Quick
2L00
O&M Rating
126
Overall Index
3
Overall Quick
Overall Rating
314
Pipe schematic from manhole 02 2255 to 02 1582
MH: 02 2255MH: 02 1582downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 22552 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start11.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start17.9 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"95 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"122.4 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"171.4 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"184.5 ft. HSV - Hole Soil Visible, from 09 to 12 o'clock, within 8 inches of joint: YES186.3 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"223.7 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"258.8 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"317.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish317.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish318.8 ft. AMH - Downstream Manhole, Survey Ends - 02 1582318.8 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    11.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Hole Soil Visible, from 09 to 12 o'clock, within 8 inches of joint: YES

    184.5 ft. - Hole Soil Visible, from 09 to 12 o'clock, within 8 inches of joint: YES

  • General Observation - COCKROACHES IN MANHOLE

    318.8 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (17)

DistanceCodeObservation
317.7DAGS
0MWL
223.7TF
17.9TF
95TF
318.8AMH02 1582
122.4TFA
318.8MGOCOCKROACHES IN MANHOLE
11.8CM
258.8TBA
186.3TB
171.4TF
0MWM
317.7CM
184.5HSV
2DAGS
0AMH02 2255

Properties (7)

additional_info
630098080322204
custom_field_three
HOLE/MULTILE CRACKS
custom_field_two
1
customer
1
datetime
2022-08-04T01:09:33-07:00
documentation
PRO PIPE
is_lateral_inspection
false