Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 4, 2022, 08:49 AM
  • 05 1519_05 1518_08042022_020659.mp4

Date
08/04/2022
W/O
967377
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00528
PipeID
P06741
Time
1:49 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10266
Sewer Name
05 TORRANCE EXTENSION TRUNK
City
TORRANCE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
29
Purpose
Routine Assessment
Project
RFIR_WO_967377_TV05309_AUG2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
15 in.
Upstream MH
05 1519
Downstream MH
05 1518
Dir. of Survey
Downstream
Length Surveyed
291.5 ft.
Total Length
291.6 ft.
Structural Index
3
Structural Quick
544K
Structural Rating
366
O&M Index
2
O&M Quick
2J00
O&M Rating
114
Overall Index
3
Overall Quick
Overall Rating
480
Pipe schematic from manhole 05 1519 to 05 1518
MH: 05 1519MH: 05 1518downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 15192 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start3.9 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start16.9 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: NO, 6", 6" - OPEN19.4 ft. B - Broken, from 07 to 02 o'clock, within 8 inches of joint: YES29.3 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN56 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES77.9 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN79.5 ft. B - Broken, from 08 to 04 o'clock, within 8 inches of joint: YES128.7 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN180.7 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN233 ft. B - Broken, from 08 to 03 o'clock, within 8 inches of joint: YES288.1 ft. B - Broken, from 08 to 12 o'clock, within 8 inches of joint: YES289 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish289 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish290.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish291.6 ft. AMH - Downstream Manhole, Survey Ends - 05 1518291.6 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/CAPPED

Observation photos (5)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.9 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 01 o'clock, -, within 8 inches of joint: NO, 6", 6" - OPEN

    16.9 ft. - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: NO, 6", 6" - OPEN

  • Broken, from 07 to 02 o'clock, within 8 inches of joint: YES

    19.4 ft. - Broken, from 07 to 02 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    56 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Broken, from 08 to 04 o'clock, within 8 inches of joint: YES

    79.5 ft. - Broken, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (21)

DistanceCodeObservation
0MWM
3.9FM
2SSS
289DAGS
16.9TBOPEN
0MWL
2DAGS
233B
291.6AMH05 1518
180.7TFOPEN
29.3TFOPEN
0AMH05 1519
79.5B
56FM
290.1FM
289SSS
288.1B
77.9TFOPEN
291.6MGOCONN @ MH 3 O'CLOCK/CAPPED
128.7TFOPEN
19.4B

Properties (7)

additional_info
630074080322202
custom_field_three
MULTIPLE CRACKS/FRACTURE'S
custom_field_two
2
customer
1
datetime
2022-08-04T01:49:58-07:00
documentation
PROPIPE
is_lateral_inspection
false