Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 4, 2022, 06:19 AM
  • 02 1464_02 1463_08032022_234251.mp4

Date
08/03/2022
W/O
967252
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00309
PipeID
P03908
Time
11:19 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10313
Sewer Name
02 UNION PACIFIC TRUNK
City
COMMERCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
17
Purpose
Routine Assessment
Project
RFIR_WO_967252_TV02355_AUG2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
24 in.
Upstream MH
02 1464
Downstream MH
02 1463
Dir. of Survey
Downstream
Length Surveyed
311.9 ft.
Total Length
311.9 ft.
Structural Index
3
Structural Quick
3J21
Structural Rating
164
O&M Index
2
O&M Quick
2K00
O&M Rating
124
Overall Index
2
Overall Quick
Overall Rating
288
Pipe schematic from manhole 02 1464 to 02 1463
MH: 02 1464MH: 02 1463downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 14640 ft. MWM - Water Mark, 10 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start18.6 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES38.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start81.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"84.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"105.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"108.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"136.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"138.5 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"157.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"159.5 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"178 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"181.3 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"206.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"209.5 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"233.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"236.5 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"257.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"260.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"281.6 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 6"285.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"305.5 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"308.8 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"309.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish309.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish311.9 ft. MGO - General Observation - COCKROACHES IN MANHOLE311.9 ft. AMH - Downstream Manhole, Survey Ends - 02 1463311.9 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    18.6 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    38.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    311.9 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (31)

DistanceCodeObservation
308.8TFC
311.9MGOCOCKROACHES IN MANHOLE
178TFC
311.9AMH02 1463
81.3TFC
2DAGS
159.5TFC
84.3TFA
181.3TFC
38.9CM
285.1TFC
108.8TFC
0MWL
138.5TFC
281.6TF
157.3TFC
309.6CM
305.5TFC
0AMH02 1464
260.4TFC
233.5TFC
257.9TFC
105.6TFC
236.5TFA
311.9MGOCONNECTION AT MH 3 O'CLOCK
309.6DAGS
18.6CL
136.2TFC
206.2TFC
0MWM
209.5TFC

Properties (7)

additional_info
630098080322203
custom_field_three
MULTIPLE CRACKS
custom_field_two
2
customer
1
datetime
2022-08-03T23:19:29-07:00
documentation
PRO PIPE
is_lateral_inspection
false