Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 16, 2022, 05:02 AM
  • 15 0925_15 0407_08152022_221908.mp4

Date
08/15/2022
W/O
967408
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00607
PipeID
P12330
Time
10:02 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10326
Sewer Name
15 HILL DRIVE EXTENSION TRUNK
City
ROSEMEAD
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
27
Purpose
Routine Assessment
Project
RFIR_WO_967408_TV15221_AUG2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
15 0925
Downstream MH
15 0407
Dir. of Survey
Downstream
Length Surveyed
249.2 ft.
Total Length
249.2 ft.
Structural Index
3
Structural Quick
413H
Structural Rating
136
O&M Index
2
O&M Quick
412I
O&M Rating
102
Overall Index
3
Overall Quick
Overall Rating
238
Pipe schematic from manhole 15 0925 to 15 0407
MH: 15 0925MH: 15 0407downstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 09252 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start24.4 ft. CM - Crack Multiple, from 11 to 03 o'clock, within 8 inches of joint: YES41.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start85.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"104.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"147.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"156.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES160.8 ft. FM - Fracture Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES206.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"219.6 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES247.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish247.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish249.2 ft. AMH - Downstream Manhole, Survey Ends - 15 0407249.2 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (7)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 11 to 03 o'clock, within 8 inches of joint: YES

    24.4 ft. - Crack Multiple, from 11 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    41.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES

    160.8 ft. - Fracture Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    219.6 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • General Observation - COCKROACHES IN MANHOLE

    249.2 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (19)

DistanceCodeObservation
247.4DAGS
2TFC
0MGOCOCKROACHES IN MANHOLE
160.8FM
0MWM
247.4CM
24.4CM
156.7FL
0MWL
249.2AMH15 0407
249.2MGOCOCKROACHES IN MANHOLE
206.3TFC
147.4TFC
219.6FL
41.2CM
0AMH15 0925
104.5TFC
85.7TFC
2DAGS

Properties (7)

additional_info
630098081522201
custom_field_three
FRACTURES/CRACKS
custom_field_two
2
customer
1
datetime
2022-08-15T22:02:54-07:00
documentation
PRO PIPE
is_lateral_inspection
false