Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 15, 2022, 10:43 AM
  • B 0349_B 0348_08152022_035515.mp4

Date
08/15/2022
W/O
962477
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00091
PipeID
P08861
Time
3:43 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10324
Sewer Name
B JOINT OUTFALL B - UNIT 5A
City
TEMPLE CITY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
15
Purpose
Routine Assessment
Project
WO_962477_TV15051_JUL2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
21 in.
Width
78 in.
Upstream MH
B 0349
Downstream MH
B 0348
Dir. of Survey
Downstream
Length Surveyed
155.1 ft.
Total Length
155.1 ft.
Structural Index
3
Structural Quick
3C00
Structural Rating
66
O&M Index
2
O&M Quick
412E
O&M Rating
64
Overall Index
2
Overall Quick
Overall Rating
130
Pipe schematic from manhole B 0349 to B 0348
MH: B 0349MH: B 0348downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 03492 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start3.9 ft. MGO - General Observation - MAG COATING41.3 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start152.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish152.7 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish155.1 ft. MGO - General Observation - COCKROACHES IN MANHOLE155.1 ft. AMH - Downstream Manhole, Survey Ends - B 0348155.1 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - MAG COATING

    3.9 ft. - General Observation - MAG COATING

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    41.3 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    155.1 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (11)

DistanceCodeObservation
41.3SAP
0MWM
155.1MGOCOCKROACHES IN MANHOLE
152.7DAGS
155.1AMHB 0348
155.1MGOCONNECTION AT MH 9 O'CLOCK
152.7SAP
0MWL
2DAGS
3.9MGOMAG COATING
0AMHB 0349

Properties (7)

additional_info
630098081522001
custom_field_three
PROJECTING AGGREGATE
custom_field_two
3
customer
1
datetime
2022-08-15T03:43:45-07:00
documentation
PRO PIPE
is_lateral_inspection
false