Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 11, 2022, 11:43 AM
  • 22 1063_22 1062_07112022_045514.mp4

Date
07/11/2022
W/O
962009
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00812
PipeID
P17434
Time
4:43 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10228
Sewer Name
22 IRWINDALE TRUNK, SECTS 2,3,4,&5
City
IRWINDALE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
18
Purpose
Capital Improvement Program Assesment
Project
RFIR_WO_962009_TV22043_JUL2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
22 1063
Downstream MH
22 1062
Dir. of Survey
Downstream
Length Surveyed
327.9 ft.
Total Length
327.9 ft.
Structural Index
3
Structural Quick
3L2L
Structural Rating
325
O&M Index
2
O&M Quick
2M00
O&M Rating
136
Overall Index
2
Overall Quick
Overall Rating
461
Pipe schematic from manhole 22 1063 to 22 1062
MH: 22 1063MH: 22 1062downstream0 ft. AMH - Upstream Manhole, Survey Begins - 22 10630 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWL - Water Level, 10 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start51.3 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"136 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"235.2 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"312.2 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 10 to 02 o'clock, , within 8 inches of joint: YES, Start325.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish325.9 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 10 to 02 o'clock, , within 8 inches of joint: YES, Finish325.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish325.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish327.9 ft. MGO - General Observation - COCKROACHES IN MANHOLE327.9 ft. AMH - Downstream Manhole, Survey Ends - 22 1062327.9 ft. MGO - General Observation - CONNECTIONS IN MH AT BOTH 3 AND 9 O' CLOCK

Observation photos (6)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 10 %of cross sectional area, from 10 to 02 o'clock,  , within 8 inches of joint: YES, Start

    312.2 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 10 to 02 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    327.9 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (18)

DistanceCodeObservation
325.9SAP
2DAGS
325.9DAGS
51.3TB
0AMH22 1063
136TB
2SAP
327.9MGOCOCKROACHES IN MANHOLE
2SSS
235.2TB
327.9AMH22 1062
0MWM
312.2DAGS
325.9SSS
0MGOCOCKROACHES IN MANHOLE
327.9MGOCONNECTIONS IN MH AT BOTH 3 AND 9 O' CLOCK
325.9DAGS
0MWL

Properties (6)

additional_info
630098071122001
custom_field_two
2
customer
1
datetime
2022-07-11T04:43:00-07:00
documentation
PRO PIPE
is_lateral_inspection
false