Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 13, 2022, 04:53 AM
  • 22 1062_22 1061_07122022_220802.mp4

Date
07/12/2022
W/O
962009
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00812
PipeID
P17433
Time
9:53 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10229
Sewer Name
22 IRWINDALE TRUNK, SECTS 2,3,4,&5
City
IRWINDALE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
24
Purpose
Capital Improvement Program Assesment
Project
RFIR_WO_962009_TV22043_JUL2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
22 1062
Downstream MH
22 1061
Dir. of Survey
Downstream
Length Surveyed
279.2 ft.
Total Length
279.2 ft.
Structural Index
3
Structural Quick
3J00
Structural Rating
165
O&M Index
2
O&M Quick
4331
O&M Rating
130
Overall Index
3
Overall Quick
Overall Rating
295
Pipe schematic from manhole 22 1062 to 22 1061
MH: 22 1062MH: 22 1061downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWM - Water Mark, 65 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 10620 ft. MGO - General Observation - CONNECTIONS IN MH AT BOTH 3 AND 9 O' CLOCK2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: YES, Start33.7 ft. RFB - Roots Fine Barrell, from 08 to 04 o'clock, within 8 inches of joint: YES, Start41 ft. RFB - Roots Fine Barrell, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish53.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"76.1 ft. RMJ - Roots Medium Joint, from 10 to 03 o'clock, 10 %, within 8 inches of joint: YESR102.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"151.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"166.5 ft. RFJ - Roots Fine Joint, from 12 to 03 o'clock, within 8 inches of joint: YESR200.8 ft. RMB - Roots Medium Barrell, from 09 to 03 o'clock, 15 %, within 8 inches of joint: YES, Start205 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"205 ft. RMB - Roots Medium Barrell, from 09 to 03 o'clock, 15 %, within 8 inches of joint: YES, Finish254.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"276.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: YES, Finish276.7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish279.2 ft. MGO - General Observation - COCKROACHES IN MANHOLE279.2 ft. AMH - Downstream Manhole, Survey Ends - 22 1061

Observation photos (8)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 02 to 10 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: YES, Start

  • Roots Fine Barrell, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    33.7 ft. - Roots Fine Barrell, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Medium Joint, from 10 to 03 o'clock, 10 %, within 8 inches of joint: YESR

    76.1 ft. - Roots Medium Joint, from 10 to 03 o'clock, 10 %, within 8 inches of joint: YESR

  • Roots Fine Joint, from 12 to 03 o'clock, within 8 inches of joint: YESR

    166.5 ft. - Roots Fine Joint, from 12 to 03 o'clock, within 8 inches of joint: YESR

  • Roots Medium Barrell, from 09 to 03 o'clock, 15 %, within 8 inches of joint: YES, Start

    200.8 ft. - Roots Medium Barrell, from 09 to 03 o'clock, 15 %, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    279.2 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (22)

DistanceCodeObservation
0MWL
151.6TFC
276.7DAGS
279.2MGOCOCKROACHES IN MANHOLE
102.6TFA
2SAP
0MGOCOCKROACHES IN MANHOLE
205TFA
41RFB
0MWM
2DAGS
254.1TF
33.7RFB
166.5RFJ
76.1RMJ
279.2AMH22 1061
200.8RMB
0AMH22 1062
276.7SAP
205RMB
53.9TF
0MGOCONNECTIONS IN MH AT BOTH 3 AND 9 O' CLOCK

Properties (7)

additional_info
630098071222201
custom_field_three
PROJECTING AGGREGATE/ROOTS
custom_field_two
2
customer
1
datetime
2022-07-12T21:53:08-07:00
documentation
PRO PIPE
is_lateral_inspection
false