Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 29, 2022, 06:48 AM
  • J 0010_J 0009_07292022_000955.mp4

Date
07/28/2022
W/O
962251
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00060
PipeID
P21401
Time
11:48 PM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K10256
Sewer Name
J JOINT OUTFALL J - UNIT 2A
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
33
Purpose
Routine Assessment
Project
RFIR_WO_962251_TV08100_JUL2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
57 in.
Width
57 in.
Upstream MH
J 0010
Downstream MH
J 0009
Dir. of Survey
Downstream
Length Surveyed
340.5 ft.
Total Length
340.5 ft.
Structural Index
2
Structural Quick
2M00
Structural Rating
136
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
136
Pipe schematic from manhole J 0010 to J 0009
MH: J 0010MH: J 0009downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK.0 ft. AMH - Upstream Manhole, Survey Begins - J 00102 ft. MGO - General Observation - MAG COATING2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start336.8 ft. TBA - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: NO, 8"340.5 ft. AMH - Downstream Manhole, Survey Ends - J 0009340.5 ft. MGO - General Observation - RAGS / OTHER COVERED "PROJECTIONS" @ D/S MH - 9 & 3 O'CLOCK.340.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (3)

  • General Observation - MAG COATING

    2 ft. - General Observation - MAG COATING

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: NO, 8"

    336.8 ft. - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: NO, 8"

Observations (10)

DistanceCodeObservation
336.8TBA
0MWM
0MWL
2MGOMAG COATING
0MGOACTIVE CONNECTION AT MH 3 O'CLOCK.
340.5AMHJ 0009
340.5MGORAGS / OTHER COVERED "PROJECTIONS" @ D/S MH - 9 & 3 O'CLOCK.
2SSS
340.5SSS
0AMHJ 0010

Properties (7)

additional_info
630098072822202
custom_field_three
SPALLING
custom_field_two
3
customer
1
datetime
2022-07-28T23:48:30-07:00
documentation
PRO PIPE
is_lateral_inspection
false