Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 29, 2022, 07:23 AM
  • J 0007_J 0006_07292022_004120.mp4

Date
07/29/2022
W/O
962251
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00060
PipeID
P21400
Time
12:23 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K10256
Sewer Name
J JOINT OUTFALL J - UNIT 2A
City
LOS ANGELES
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
16
Purpose
Routine Assessment
Project
RFIR_WO_962251_TV08100_JUL2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
57 in.
Width
57 in.
Upstream MH
J 0007
Downstream MH
J 0006
Dir. of Survey
Downstream
Length Surveyed
422.1 ft.
Total Length
422.1 ft.
Structural Index
2
Structural Quick
2P00
Structural Rating
168
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
170
Pipe schematic from manhole J 0007 to J 0006
MH: J 0007MH: J 0006downstream0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK.0 ft. AMH - Upstream Manhole, Survey Begins - J 00070 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. MGO - General Observation - MAG COATING58.4 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 8"74.2 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 8"237.9 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: NO, 8" - ACTIVE CONNECTION.237.9 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 12"259.3 ft. TBI - Tap Break-In Intruding, at 10 o'clock, -, #v, within 8 inches of joint: NO, 10", 2"388.8 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 8"422.1 ft. AMH - Downstream Manhole, Survey Ends - J 0006422.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (8)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - MAG COATING

    2 ft. - General Observation - MAG COATING

  • Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 8"

    58.4 ft. - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 8"

  • Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 8"

    74.2 ft. - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 8"

  • Tap Break-In, at 11 o'clock, -, within 8 inches of joint: NO, 8" - ACTIVE CONNECTION.

    237.9 ft. - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: NO, 8" - ACTIVE CONNECTION.

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 12"

    237.9 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 12"

  • Tap Break-In Intruding, at 10 o'clock, -, #v, within 8 inches of joint: NO, 10", 2"

    259.3 ft. - Tap Break-In Intruding, at 10 o'clock, -, #v, within 8 inches of joint: NO, 10", 2"

  • Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 8"

    388.8 ft. - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 8"

Observations (14)

DistanceCodeObservation
2SSS
0MGOACTIVE CONNECTION AT MH 9 O'CLOCK.
58.4TB
259.3TBI
422.1AMHJ 0006
422.1SSS
0AMHJ 0007
0MWM
74.2TB
237.9TBACTIVE CONNECTION.
2MGOMAG COATING
0MWL
237.9TB
388.8TBA

Properties (7)

additional_info
630098072822202
custom_field_three
SPALLING
custom_field_two
3
customer
1
datetime
2022-07-29T00:23:24-07:00
documentation
PRO PIPE
is_lateral_inspection
false