Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 29, 2022, 07:10 AM
  • J 0009_J 0007_07292022_002117.mp4

Date
07/29/2022
W/O
962251
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00060
PipeID
P11595
Time
12:10 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K10256
Sewer Name
J JOINT OUTFALL J - UNIT 2A
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
16
Purpose
Routine Assessment
Project
RFIR_WO_962251_TV08100_JUL2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
57 in.
Width
57 in.
Upstream MH
J 0009
Downstream MH
J 0007
Dir. of Survey
Downstream
Length Surveyed
325.9 ft.
Total Length
325.9 ft.
Structural Index
2
Structural Quick
2L00
Structural Rating
130
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
130
Pipe schematic from manhole J 0009 to J 0007
MH: J 0009MH: J 0007downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - J 00092 ft. MGO - General Observation - MAG COATING2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start123.3 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 8"220.6 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 8" - ACTIVE CONN.325.9 ft. AMH - Downstream Manhole, Survey Ends - J 0007325.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish325.9 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK.

Observation photos (4)

  • General Observation - MAG COATING

    2 ft. - General Observation - MAG COATING

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 8"

    123.3 ft. - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 8"

  • Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 8" - ACTIVE CONN.

    220.6 ft. - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 8" - ACTIVE CONN.

Observations (10)

DistanceCodeObservation
0MWL
325.9AMHJ 0007
325.9SSS
0MWM
2MGOMAG COATING
325.9MGOACTIVE CONNECTION AT MH 9 O'CLOCK.
123.3TB
0AMHJ 0009
2SSS
220.6TBACTIVE CONN.

Properties (7)

additional_info
630098072822202
custom_field_three
SPALLING
custom_field_two
3
customer
1
datetime
2022-07-29T00:10:10-07:00
documentation
PRO PIPE
is_lateral_inspection
false