Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 29, 2022, 08:54 AM
  • J 0006_J 0005_07292022_021522.mp4

Date
07/29/2022
W/O
962251
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00060
PipeID
P11594
Time
1:54 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K10256
Sewer Name
J JOINT OUTFALL J - UNIT 2A
City
LOS ANGELES
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_962251_TV08100_JUL2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
57 in.
Width
57 in.
Upstream MH
J 0006
Downstream MH
J 0005
Dir. of Survey
Downstream
Length Surveyed
647.4 ft.
Total Length
647.4 ft.
Structural Index
2
Structural Quick
2Y00
Structural Rating
258
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
258
Pipe schematic from manhole J 0006 to J 0005
MH: J 0006MH: J 0005downstream0 ft. AMH - Upstream Manhole, Survey Begins - J 00060 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. MGO - General Observation - MAG COATING647.4 ft. MGO - General Observation - CONNECTIONS IN MH AT BOTH 3 AND 9 O' CLOCK (CONN. @ 3 O'CLK. "VISIBLY" ACTIVE.)647.4 ft. AMH - Downstream Manhole, Survey Ends - J 0005647.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (2)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - MAG COATING

    2 ft. - General Observation - MAG COATING

Observations (8)

DistanceCodeObservation
0AMHJ 0006
0MWM
2SSS
647.4MGOCONNECTIONS IN MH AT BOTH 3 AND 9 O' CLOCK (CONN. @ 3 O'CLK. "VISIBLY" ACTIVE.)
2MGOMAG COATING
647.4AMHJ 0005
647.4SSS
0MWL

Properties (7)

additional_info
630098072822202
custom_field_three
SPALLING
custom_field_two
3
customer
1
datetime
2022-07-29T01:54:24-07:00
documentation
PRO PIPE
is_lateral_inspection
false