Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 1, 2022, 08:47 AM
  • J 0002_J 0001_08012022_020440.mp4

Date
08/01/2022
W/O
962251
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00060
PipeID
P11589
Time
1:47 AM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K10257
Sewer Name
J JOINT OUTFALL J - UNIT 2A
City
HARBOR CITY
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_962251_TV08100_JUL2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
57 in.
Width
57 in.
Upstream MH
J 0002
Downstream MH
J 0001
Dir. of Survey
Downstream
Length Surveyed
377.7 ft.
Total Length
377.7 ft.
Structural Index
3
Structural Quick
3N2N
Structural Rating
370
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
370
Pipe schematic from manhole J 0002 to J 0001
MH: J 0002MH: J 0001downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - J00020 ft. MWL - Water Level, 25 %of cross sectional area4.4 ft. MGO - General Observation - MAG COATING4.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start4.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start374 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish374 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish377.7 ft. AMH - Downstream Manhole, Survey Ends - J 0001

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.4 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.4 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
0MWM
0AMHJ0002
374SAP
377.7AMHJ 0001
4.4MGOMAG COATING
374SSS
0MWL
4.4SAP
4.4SSS

Properties (7)

additional_info
6300980801220001
custom_field_three
AGGREGATE PROJECTING, SPALLING
custom_field_two
3
customer
1
datetime
2022-08-01T01:47:01-07:00
documentation
PROPIPE
is_lateral_inspection
false