Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 14, 2022, 06:19 AM
  • 18 0924_18 0094_07132022_232342.mp4

Date
07/13/2022
W/O
961788
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00700
PipeID
P14772
Time
11:19 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10230
Sewer Name
18 SCOTT AVENUE TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_961788_TV18047_JUL2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 0924
Downstream MH
18 0094
Dir. of Survey
Downstream
Length Surveyed
24.8 ft.
Total Length
24.8 ft.
Structural Index
3
Structural Quick
3400
Structural Rating
12
O&M Index
2
O&M Quick
2400
O&M Rating
8
Overall Index
3
Overall Quick
Overall Rating
20
Pipe schematic from manhole 18 0924 to 18 0094
MH: 18 0924MH: 18 0094downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 09240 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start22.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish22.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish24.8 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK24.8 ft. AMH - Downstream Manhole, Survey Ends - 18 009424.8 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    24.8 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (10)

DistanceCodeObservation
0AMH18 0924
24.8MGOCONNECTION AT MH 9 O'CLOCK
0MWL
2DAGS
24.8AMH18 0094
4CM
24.8MGOCOCKROACHES IN MANHOLE
22.5DAGS
0MWM
22.5CM

Properties (7)

additional_info
630098071322201
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2022-07-13T23:19:35-07:00
documentation
PRO PIPE
is_lateral_inspection
false