Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 10, 2022, 04:55 AM
  • 18 0827_18 0826_08092022_220535.mp4

Date
08/09/2022
W/O
966850
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00707
PipeID
P14690
Time
9:55 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10319
Sewer Name
18 SO WHITTIER OUTFALL TR, SECT 5
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
20
Purpose
Routine Assessment
Project
RFIR_WO_966850_TV18119_AUG2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 0827
Downstream MH
18 0826
Dir. of Survey
Downstream
Length Surveyed
95.1 ft.
Total Length
95.1 ft.
Structural Index
3
Structural Quick
3C00
Structural Rating
54
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
54
Pipe schematic from manhole 18 0827 to 18 0826
MH: 18 0827MH: 18 0826downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 08273 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start31.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"35.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"81.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"85 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"92.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish95.1 ft. MGO - General Observation - COCKROACHES IN MANHOLE95.1 ft. AMH - Downstream Manhole, Survey Ends - 18 082695.1 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    95.1 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (12)

DistanceCodeObservation
0MWM
95.1MGOCOCKROACHES IN MANHOLE
0MWL
85TFC
35.5TFC
31.6TFA
0AMH18 0827
81.8TFC
3CM
92.5CM
95.1AMH18 0826
95.1MGOCONNECTION AT MH 3 O'CLOCK

Properties (7)

additional_info
630098080922201
custom_field_three
MULTIPLE CRACKS
custom_field_two
2
customer
1
datetime
2022-08-09T21:55:48-07:00
documentation
PRO PIPE
is_lateral_inspection
false