Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 10, 2022, 05:18 AM
  • 18 0825_18 0824_08092022_222627.mp4

Date
08/09/2022
W/O
966850
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00707
PipeID
P14688
Time
10:18 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10319
Sewer Name
18 SO WHITTIER OUTFALL TR, SECT 5
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
20
Purpose
Routine Assessment
Project
RFIR_WO_966850_TV18119_AUG2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 0825
Downstream MH
18 0824
Dir. of Survey
Downstream
Length Surveyed
126.7 ft.
Total Length
126.7 ft.
Structural Index
3
Structural Quick
3D00
Structural Rating
72
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
72
Pipe schematic from manhole 18 0825 to 18 0824
MH: 18 0825MH: 18 0824downstream0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Begins - 18 08250 ft. MWM - Water Mark, 15 %of cross sectional area6.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start25 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"28.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"77.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"81.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"118.1 ft. TBA - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"126.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish126.7 ft. AMH - Downstream Manhole, Survey Ends - 18 0824

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
77.9TFA
0MGOCONNECTION AT MH 3 O'CLOCK
0MWL
6.6CM
0MGOCOCKROACHES IN MANHOLE
28.4TFC
118.1TBA
25TFC
0AMH18 0825
81.1TFC
126.7CM
126.7AMH18 0824
0MWM

Properties (7)

additional_info
630098080922201
custom_field_three
MULTIPLE CRACKS
custom_field_two
2
customer
1
datetime
2022-08-09T22:18:39-07:00
documentation
PRO PIPE
is_lateral_inspection
false