Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 12, 2022, 07:31 AM
  • 01 0217_01 0216_08122022_004817.mp4

Date
08/12/2022
W/O
966853
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00202
PipeID
P01259
Time
12:31 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10280
Sewer Name
01 COMPTON AVENUE TRUNK
City
LOS ANGELES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
06
Purpose
Routine Assessment
Project
RFIR_WO_966853_TV01222_AUG2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
15 in.
Upstream MH
01 0217
Downstream MH
01 0216
Dir. of Survey
Downstream
Length Surveyed
381.4 ft.
Total Length
381.4 ft.
Structural Index
4
Structural Quick
4131
Structural Rating
7
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
3
Overall Quick
Overall Rating
8
Pipe schematic from manhole 01 0217 to 01 0216
MH: 01 0217MH: 01 0216downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 01 02170 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - SEWER SNAKE IN MH3.7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start30.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"71.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"91.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"126.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"154.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"210.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"225.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"232.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"260.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"293.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"294.4 ft. RFJ - Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YES313.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"354.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"355.7 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES379.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish381.4 ft. AMH - Downstream Manhole, Survey Ends - 01 0216381.4 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK

Observation photos (4)

  • General Observation - SEWER SNAKE IN MH

    0 ft. - General Observation - SEWER SNAKE IN MH

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.7 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YES

    294.4 ft. - Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    355.7 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

Observations (24)

DistanceCodeObservation
0MWM
154.5TF
30.3TF
232.8TF
260.7TF
71.7TF
91.2TF
0MGOCONNECTION AT MH 9 O'CLOCK
0AMH01 0217
126.8TF
0MGOCONNECTION AT MH 3 O'CLOCK
355.7FM
3.7SAP
225.4TF
210.1TF
381.4AMH01 0216
381.4MGOCONNECTION AT MH 9 O'CLOCK
293.4TF
0MWL
379.1SAP
313.8TF
0MGOSEWER SNAKE IN MH
294.4RFJ
354.4TF

Properties (7)

additional_info
630074081122202
custom_field_three
AGGREGATE PROJECTING
custom_field_two
2
customer
1
datetime
2022-08-12T00:31:44-07:00
documentation
PROPIPE
is_lateral_inspection
false