- Date
- 08/12/2022
- W/O
- 966853
- Weather
- Dry
- Operator/Surveyor
- B.FUGATE
- Sewer ID
- Z00202
- PipeID
- P01259
- Time
- 12:31 AM
- Certificate
- U-508-7069
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K10280
- Sewer Name
- 01 COMPTON AVENUE TRUNK
- City
- LOS ANGELES
- Loc. details
- Main Highway - Urban
- Location Code
- A
- Use of Sewer
- Sanitary Sewer
- District
- District 01
- Page No.
- 06
- Purpose
- Routine Assessment
- Project
- RFIR_WO_966853_TV01222_AUG2022
- Sewer Type
- Gravity
- Material
- NRCP
- Shape
- Circular
- Height
- 12 in.
- Width
- 15 in.
- Upstream MH
- 01 0217
- Downstream MH
- 01 0216
- Dir. of Survey
- Downstream
- Length Surveyed
- 381.4 ft.
- Total Length
- 381.4 ft.
- Structural Index
- 4
- Structural Quick
- 4131
- Structural Rating
- 7
- O&M Index
- 1
- O&M Quick
- 1100
- O&M Rating
- 1
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 8
Pipe schematic from manhole 01 0217 to 01 0216 Observation photos (4)

0 ft. - General Observation - SEWER SNAKE IN MH

3.7 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

294.4 ft. - Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YES

355.7 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES