Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 24, 2022, 09:06 AM
  • 02 1420_02 1419_05242022_021320.mp4

Date
05/24/2022
W/O
951971
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00349
PipeID
P02991
Time
2:06 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10125
Sewer Name
02 DISTRICT #2 INTERCEPTOR TRUNK
City
COMMERCE
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
17
Purpose
Routine Assessment
Project
RFIR_WO_951971_TV02220_MAY2022
Sewer Type
Siphon
Material
Reinforced Concrete Pipe
Shape
Circular
Height
54 in.
Width
33 in.
Upstream MH
02 1420
Downstream MH
02 1419
Dir. of Survey
Downstream
Length Surveyed
2 ft.
Total Length
2 ft.
Structural Index
3
Structural Quick
5131
Structural Rating
10
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
4
Overall Quick
Overall Rating
14
Pipe schematic from manhole 02 1420 to 02 1419
MH: 02 1420MH: 02 1419downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 14200 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 30 %of cross sectional area2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES2 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES2 ft. MSA - Survey Abandoned - VIEW OF DOWNLEG OF U/S SIPHON.2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES

Observation photos (4)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES

    2 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Survey Abandoned - VIEW OF DOWNLEG OF U/S SIPHON.

    2 ft. - Survey Abandoned - VIEW OF DOWNLEG OF U/S SIPHON.

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES

Observations (7)

DistanceCodeObservation
2SAP
0AMH02 1420
0MWM
2SRV
2MSAVIEW OF DOWNLEG OF U/S SIPHON.
0MWL
2SSS

Properties (7)

additional_info
630074052322203
custom_field_three
VISIBLE REINFORCEMENT/PROJECTING AGGREGATE
custom_field_two
2
customer
1
datetime
2022-05-24T02:06:07-07:00
documentation
PRO PIPE
is_lateral_inspection
false