Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 11, 2022, 04:48 AM
  • H 0277_H 0276_08102022_222028.mp4

Date
08/10/2022
W/O
962077
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00173
PipeID
P10733
Time
9:48 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10275
Sewer Name
H JOINT OUTFALL H - UNIT 2H
City
VERNON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 23
Page No.
01
Purpose
Routine Assessment
Project
RFIR_WO_962077_TV23005_JUL2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
H 0277
Downstream MH
H 0276
Dir. of Survey
Downstream
Length Surveyed
266.5 ft.
Total Length
266.5 ft.
Structural Index
3
Structural Quick
4121
Structural Rating
6
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
2
Overall Quick
Overall Rating
7
Pipe schematic from manhole H 0277 to H 0276
MH: H 0277MH: H 0276downstream0 ft. VC - Vermin Cockroach0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 027712.6 ft. TSC - Tap Saddle Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"73.5 ft. TSC - Tap Saddle Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"82 ft. TSC - Tap Saddle Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"154.8 ft. TSC - Tap Saddle Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"161.3 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES161.8 ft. TB - Tap Break-In, at 03 o'clock, -, within 8 inches of joint: NO, 6"232.9 ft. FM - Fracture Multiple, from 08 to 05 o'clock, within 8 inches of joint: YES234.2 ft. TS - Tap Saddle, at 10 o'clock, -, within 8 inches of joint: NO, 6"242.8 ft. TB - Tap Break-In, at 03 o'clock, -, within 8 inches of joint: YES, 6"266.5 ft. AMH - Downstream Manhole, Survey Ends - H 0276

Observation photos (5)

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    161.3 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Tap Break-In, at 03 o'clock, -, within 8 inches of joint: NO, 6"

    161.8 ft. - Tap Break-In, at 03 o'clock, -, within 8 inches of joint: NO, 6"

  • Fracture Multiple, from 08 to 05 o'clock, within 8 inches of joint: YES

    232.9 ft. - Fracture Multiple, from 08 to 05 o'clock, within 8 inches of joint: YES

  • Tap Saddle, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    234.2 ft. - Tap Saddle, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 03 o'clock, -, within 8 inches of joint: YES, 6"

    242.8 ft. - Tap Break-In, at 03 o'clock, -, within 8 inches of joint: YES, 6"

Observations (15)

DistanceCodeObservation
73.5TSC
234.2TS
82TSC
232.9FM
0VC
161.8TB
0MGOCONNECTION AT MH 9 O'CLOCK
161.3CL
242.8TB
0MWL
12.6TSC
0MWM
0AMHH 0277
266.5AMHH 0276
154.8TSC

Properties (7)

additional_info
630074081022201
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2022-08-10T21:48:38-07:00
documentation
PROPIPE
is_lateral_inspection
false