Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 14, 2022, 09:58 AM
  • 18 0503_18 0502_07142022_031224.mp4

Date
07/14/2022
W/O
962069
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00705
PipeID
P14357
Time
2:58 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10232
Sewer Name
18 SOUTH PLANT OUTFALL TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
14
Purpose
Routine Assessment
Project
RFIR_WO_962069_TV18180_JUL2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
18 0503
Downstream MH
18 0502
Dir. of Survey
Downstream
Length Surveyed
505.1 ft.
Total Length
505.1 ft.
Structural Index
3
Structural Quick
3S00
Structural Rating
294
O&M Index
2
O&M Quick
2S00
O&M Rating
200
Overall Index
2
Overall Quick
Overall Rating
494
Pipe schematic from manhole 18 0503 to 18 0502
MH: 18 0503MH: 18 0502downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 05032 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start15.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start53.5 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"90.8 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"141.3 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"378.3 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"390.6 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"503.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish503.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish505.1 ft. AMH - Downstream Manhole, Survey Ends - 18 0502505.1 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    15.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    505.1 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (14)

DistanceCodeObservation
503.1DAGS
0MWL
390.6TBA
0MWM
0AMH18 0503
503.1CM
15.3CM
141.3TBA
53.5TBA
2DAGS
505.1AMH18 0502
505.1MGOCOCKROACHES IN MANHOLE
90.8TBA
378.3TBA

Properties (7)

additional_info
630098071322203
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2022-07-14T02:58:26-07:00
documentation
PRO PIPE
is_lateral_inspection
false