Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 29, 2022, 09:20 AM
  • 17 0096_17 0095_07292022_023705.mp4

Date
07/29/2022
W/O
962223
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00669
PipeID
P13814
Time
2:20 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10305
Sewer Name
17 LINCOLN AVENUE TRUNK
City
ALTADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 17
Page No.
01
Purpose
Routine Assessment
Project
WO_962223_TV17002_JUL2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
17 0096
Downstream MH
17 0095
Dir. of Survey
Downstream
Length Surveyed
342.2 ft.
Total Length
342.2 ft.
Structural Index
3
Structural Quick
3C24
Structural Rating
65
O&M Index
2
O&M Quick
2M00
O&M Rating
136
Overall Index
2
Overall Quick
Overall Rating
201
Pipe schematic from manhole 17 0096 to 17 0095
MH: 17 0096MH: 17 0095downstream0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK.0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 17 00960 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MH2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start23.7 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"96.9 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Start105.3 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Finish116.6 ft. CL - Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES121.7 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"235.6 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES247.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start252.3 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"319.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"340.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish340.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish342.2 ft. MGO - General Observation - COCKROACHES IN MH342.2 ft. AMH - Downstream Manhole, Survey Ends - 17 0095

Observation photos (6)

  • General Observation - COCKROACHES IN MH

    0 ft. - General Observation - COCKROACHES IN MH

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Start

    96.9 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES

    116.6 ft. - Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    247.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MH

    342.2 ft. - General Observation - COCKROACHES IN MH

Observations (19)

DistanceCodeObservation
0MGOACTIVE CONNECTION AT MH 9 O'CLOCK.
0MWL
342.2MGOCOCKROACHES IN MH
342.2AMH17 0095
340.4DAGS
252.3TFA
247.9CM
23.7TFC
319.5TFC
235.6CL
0AMH17 0096
96.9CL
105.3CL
116.6CL
0MWM
0MGOCOCKROACHES IN MH
2DAGS
340.4CM
121.7TFA

Properties (7)

additional_info
630074072822205
custom_field_three
MULTIPLE CRACKS.
custom_field_two
3
customer
1
datetime
2022-07-29T02:20:37-07:00
documentation
PRO PIPE
is_lateral_inspection
false