Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 29, 2022, 08:45 AM
  • 17 0093_17 0092_07292022_015941.mp4

Date
07/29/2022
W/O
962223
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00669
PipeID
P13811
Time
1:45 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10305
Sewer Name
17 LINCOLN AVENUE TRUNK
City
ALTADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 17
Page No.
01
Purpose
Routine Assessment
Project
WO_962223_TV17002_JUL2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
17 0092
Downstream MH
17 0093
Dir. of Survey
Upstream
Length Surveyed
316 ft.
Total Length
316 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2111
O&M Rating
3
Overall Index
2
Overall Quick
Overall Rating
6
Pipe schematic from manhole 17 0092 to 17 0093
MH: 17 0092MH: 17 0093upstream0 ft. AMH - Upstream Manhole, Survey Ends - 17 00930 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK.2.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish2.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish19.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"33.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"91.6 ft. RFJ - Roots Fine Joint, from 03 to 05 o'clock, within 8 inches of joint: YES116.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"118.8 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"165.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"180.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"214.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"237.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"263.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"282.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"296.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start304.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"314 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start316 ft. MWL - Water Level, 5 %of cross sectional area316 ft. MWM - Water Mark, 20 %of cross sectional area316 ft. AMH - Downstream Manhole, Survey Begins - 17 0092

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    19.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, from 03 to 05 o'clock, within 8 inches of joint: YES

    224.4 ft. - Roots Fine Joint, from 03 to 05 o'clock, within 8 inches of joint: YES

Observations (21)

DistanceCodeObservation
52.5TFC
19.9CM
11.2TFC
150.5TFA
296.9TFA
313.8DAGS
101.3TFA
78.7TF
316AMH17 0093
33.8TF
2DAGS
316MGOACTIVE CONNECTION AT MH 3 O'CLOCK.
0MWL
199.8TFA
224.4RFJ
313.8CM
135.7TFC
0MWM
282.5TFA
0AMH17 0092
197.2TFA

Properties (7)

additional_info
630074072822205
custom_field_three
CRACK MULTIPLE.
custom_field_two
3
customer
1
datetime
2022-07-29T01:45:49-07:00
documentation
PRO PIPE
is_lateral_inspection
false