Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 14, 2022, 05:02 AM
  • 03 0059_03 0058_07132022_221826.mp4

Date
07/13/2022
W/O
962049
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00366
PipeID
P05080
Time
10:02 PM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9979
Sewer Name
03 LOS COYOTES DIAGONAL TRUNK
City
LAKEWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
09
Purpose
Routine Assessment
Project
RFIR_WO_962049_TV03117_JUL2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
18 in.
Upstream MH
03 0059
Downstream MH
03 0058
Dir. of Survey
Downstream
Length Surveyed
330.5 ft.
Total Length
330.6 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole 03 0059 to 03 0058
MH: 03 0059MH: 03 0058downstream0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 03 00590 ft. MWL - Water Level, 40 %of cross sectional area8.1 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start95.7 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 8", 8"196.9 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 6"250.8 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"320.2 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Finish330.6 ft. AMH - Downstream Manhole, Survey Ends - 03 0058

Observation photos (4)

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock,  , within 8 inches of joint: YES, Start

    8.1 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start

  • Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 8", 8"

    95.7 ft. - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 8", 8"

  • Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 6"

    196.9 ft. - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"

    250.8 ft. - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"

Observations (10)

DistanceCodeObservation
8.1DAE
330.6AMH03 0058
196.9TB
0MGOCONNECTION AT MH 9 O'CLOCK
0MWM
0AMH03 0059
95.7TBA
0MWL
320.2DAE
250.8TBA

Properties (7)

additional_info
630074071322201
custom_field_three
ENCRUSTATION
custom_field_two
3
customer
1
datetime
2022-07-13T22:02:33-07:00
documentation
PRO PIPE
is_lateral_inspection
false