Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 14, 2022, 06:59 AM
  • 03 0047_03 0046_07142022_001703.mp4

Date
07/13/2022
W/O
962049
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00366
PipeID
P05067
Time
11:59 PM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9979
Sewer Name
03 LOS COYOTES DIAGONAL TRUNK
City
LAKEWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
09
Purpose
Routine Assessment
Project
RFIR_WO_962049_TV03117_JUL2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
24 in.
Upstream MH
03 0047
Downstream MH
03 0046
Dir. of Survey
Downstream
Length Surveyed
324.6 ft.
Total Length
324.6 ft.
Structural Index
2
Structural Quick
3123
Structural Rating
9
O&M Index
2
O&M Quick
2300
O&M Rating
6
Overall Index
2
Overall Quick
Overall Rating
15
Pipe schematic from manhole 03 0047 to 03 0046
MH: 03 0047MH: 03 0046downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 03 00472 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: NO12.9 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES20.9 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start23.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"58.5 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: NO58.5 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6"61.1 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES64.7 ft. CS - Crack Spiral, from 10 to 12 o'clock, within 8 inches of joint: YES130.5 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6"166 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6"221.7 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6"265.2 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6"316.6 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6"317.7 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES324.6 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish324.6 ft. AMH - Downstream Manhole, Survey Ends - 03 0046

Observation photos (13)

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: NO

    2 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: NO

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES

    12.9 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    20.9 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: NO

    58.5 ft. - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: NO

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6"

    58.5 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6"

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    61.1 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 10 to 12 o'clock, within 8 inches of joint: YES

    64.7 ft. - Crack Spiral, from 10 to 12 o'clock, within 8 inches of joint: YES

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6"

    130.5 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6"

    166 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6"

    221.7 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6"

    265.2 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6"

    316.6 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6"

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    317.7 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

Observations (19)

DistanceCodeObservation
0MWM
265.2TB
0MWL
12.9DAE
316.6TB
61.1CL
324.6DAE
130.5TB
2DAE
166TB
324.6AMH03 0046
317.7CL
0AMH03 0047
58.5FL
64.7CS
221.7TB
58.5TB
23.2TF
20.9DAE

Properties (7)

additional_info
630074071322201
custom_field_three
ENCRUSTATION, CRACKS
custom_field_two
3
customer
1
datetime
2022-07-13T23:59:16-07:00
documentation
PRO PIPE
is_lateral_inspection
false