Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 3, 2022, 06:31 AM
  • H 0869_H 0489A_08022022_234951.mp4

Date
08/02/2022
W/O
961757
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00181
PipeID
P20460
Time
11:31 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10308
Sewer Name
H JOINT OUTFALL H - UNIT 6
City
CITY OF INDUSTRY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
29
Purpose
Routine Assessment
Project
RFIR_WO_961757_TV15212_JUL2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
54 in.
Width
54 in.
Upstream MH
H 0869
Downstream MH
H 0489A
Dir. of Survey
Downstream
Length Surveyed
358 ft.
Total Length
358 ft.
Structural Index
3
Structural Quick
5131
Structural Rating
10
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
10
Pipe schematic from manhole H 0869 to H 0489A
MH: H 0869MH: H 0489Adownstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - STOP LOG CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - H 08690 ft. MWM - Water Mark, 20 %of cross sectional area6.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start6.3 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start82.8 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"115.7 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start353.3 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish353.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish353.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish358 ft. AMH - Downstream Manhole, Survey Ends - H 0489A

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.3 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.3 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
353.3SRV
0MWL
353.3SAP
115.7SSS
82.8TBA
353.3SSS
358AMHH 0489A
0MGOSTOP LOG CONNECTION AT MH 3 O'CLOCK
6.3SAP
0AMHH 0869
6.3SRV
0MWM

Properties (7)

additional_info
630074080222202
custom_field_three
VISIBLE REINFORCEMENT/PROJECTING AGGREGATE
custom_field_two
2
customer
1
datetime
2022-08-02T23:31:19-07:00
documentation
PRO PIPE
is_lateral_inspection
false