Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 3, 2022, 06:22 AM
  • H 0490_H 0869_08022022_233102.mp4

Date
08/02/2022
W/O
961757
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00181
PipeID
P10916
Time
11:22 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10308
Sewer Name
H JOINT OUTFALL H - UNIT 6
City
LA PUENTE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
29
Purpose
Routine Assessment
Project
RFIR_WO_961757_TV15212_JUL2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
54 in.
Width
54 in.
Upstream MH
H 0490
Downstream MH
H 0869
Dir. of Survey
Downstream
Length Surveyed
34.7 ft.
Total Length
34.7 ft.
Structural Index
3
Structural Quick
5131
Structural Rating
10
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
10
Pipe schematic from manhole H 0490 to H 0869
MH: H 0490MH: H 0869downstream0 ft. AMH - Upstream Manhole, Survey Begins - H 04900 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start30.1 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish30.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish30.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish34.7 ft. MGO - General Observation - STOP LOG CONNECTION AT MH 3 O'CLOCK34.7 ft. AMH - Downstream Manhole, Survey Ends - H 0869

Observation photos (3)

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
0AMHH 0490
0MWM
30.1SRV
2SRV
34.7MGOSTOP LOG CONNECTION AT MH 3 O'CLOCK
30.1SSS
30.1SAP
34.7AMHH 0869
2SSS
2SAP
0MWL

Properties (7)

additional_info
630074080222202
custom_field_three
VISIBLE REINFORCEMENT/PROJECTING AGGREGATE
custom_field_two
2
customer
1
datetime
2022-08-02T23:22:14-07:00
documentation
PRO PIPE
is_lateral_inspection
false