Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 3, 2022, 10:00 AM
  • B 1161_B 1160_08032022_031407.mp4

Date
08/03/2022
W/O
962066
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z01125
PipeID
P13481
Time
3:00 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10310
Sewer Name
B JOINT OUTFALL B - UNIT 6H
City
SOUTH PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
20
Purpose
Routine Assessment
Project
RFIR_WO_962066_TV16118_JUL2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
16 in.
Width
16 in.
Upstream MH
B 1161
Downstream MH
B 1160
Dir. of Survey
Downstream
Length Surveyed
313.8 ft.
Total Length
313.8 ft.
Structural Index
3
Structural Quick
3K00
Structural Rating
186
O&M Index
2
O&M Quick
2L00
O&M Rating
126
Overall Index
3
Overall Quick
Overall Rating
312
Pipe schematic from manhole B 1161 to B 1160
MH: B 1161MH: B 1160downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 11610 ft. MGO - General Observation - COCKROACHES IN MH2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start12.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"20.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"62.1 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6"72.3 ft. TBA - Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"111 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"123.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"128 ft. TBA - Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: YES, 6"161.3 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"171.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"214.7 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"222.4 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"263.1 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"271.1 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6", 6"311.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish311.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish313.8 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK313.8 ft. AMH - Downstream Manhole, Survey Ends - B 1160

Observation photos (3)

  • General Observation - COCKROACHES IN MH

    0 ft. - General Observation - COCKROACHES IN MH

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (23)

DistanceCodeObservation
171.6TF
214.7TFA
311.8CM
111TFA
0MWM
0MWL
263.1TFA
2DAGS
222.4TFA
12.6TFA
161.3TFA
123.7TFC
0AMHB 1161
20.3TFA
72.3TBA
2CM
128TBA
62.1TFD
271.1TFC
313.8MGOCONNECTION AT MH 9 O'CLOCK
311.8DAGS
313.8AMHB 1160
0MGOCOCKROACHES IN MH

Properties (7)

additional_info
630074080222204
custom_field_three
MULTIPLE CRACKS
custom_field_two
2
customer
1
datetime
2022-08-03T03:00:29-07:00
documentation
PRO PIPE
is_lateral_inspection
false