Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 28, 2022, 04:58 AM
  • 02 1788_02 2411_07272022_221633.mp4

Date
07/27/2022
W/O
961745
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00274
PipeID
P21173
Time
9:58 PM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9994
Sewer Name
02 INDIANA STREET P.P. CONNECTIONS
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
07A
Purpose
Routine Assessment
Project
RFIR_WO_961745_TV02400_JUL2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 1788
Downstream MH
02 2411
Dir. of Survey
Downstream
Length Surveyed
454.2 ft.
Total Length
454.2 ft.
Structural Index
2
Structural Quick
3O2P
Structural Rating
409
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
409
Pipe schematic from manhole 02 1788 to 02 2411
MH: 02 1788MH: 02 2411downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 17880 ft. MWL - Water Level, 10 %of cross sectional area21.7 ft. CL - Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES38.8 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES44.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start44.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - VCP SPALLING.447.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish447.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - VCP SPALLING.454.2 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 12 O'CLOCK.454.2 ft. AMH - Downstream Manhole, Survey Ends - 02 2411

Observation photos (3)

  • Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES

    21.7 ft. - Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    38.8 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    44.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
0MWM
447.5CM
21.7CL
44.6CM
0AMH02 1788
447.5SSSVCP SPALLING.
454.2MGOACTIVE CONNECTION AT MH 12 O'CLOCK.
38.8CL
454.2AMH02 2411
44.6SSSVCP SPALLING.
0MWL

Properties (7)

additional_info
630098072722201
custom_field_three
CRACKS - VCP SPALLING.
custom_field_two
3
customer
1
datetime
2022-07-27T21:58:16-07:00
documentation
PRO PIPE
is_lateral_inspection
false