Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 6, 2022, 11:06 AM
  • 18 0368_F 0302_962022_052618.mp4

Date
09/06/2022
W/O
0972524
Weather
Dry
Operator/Surveyor
SANTIAGO OBREGON
Sewer ID
Z00690
PipeID
P14202
Time
4:06 AM
Certificate
U-1014-06022541
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H3192
Sewer Name
18 NORTH NORWALK TRUNK
City
NORWALK
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
30
Purpose
Capital Improvement Program Assesment
Project
20220906_SHO_N_NRWK_TR
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
18 0368
Downstream MH
F 0302
Dir. of Survey
Downstream
Length Surveyed
25.1 ft.
Total Length
25.1 ft.
Structural Index
5
Structural Quick
5141
Structural Rating
9
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
5
Overall Quick
Overall Rating
9
Pipe schematic from manhole 18 0368 to F 0302
MH: 18 0368MH: F 0302downstream0 ft. AMH - Upstream Manhole, Survey Begins - MH 3680 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start20.8 ft. B - Broken, from 08 to 11 o'clock, within 8 inches of joint: YES24 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish25.1 ft. AMH - Downstream Manhole, Survey Ends - MH F 302

Observations (7)

DistanceCodeObservation
0AMHMH 368
20.8B
0MWL
0MWM
25.1AMHMH F 302
4FM
24FM

Properties (7)

additional_info
RFIR
custom_field_three
RFIR
custom_field_two
3
customer
LACSD
datetime
2022-09-06T04:06:08-07:00
documentation
OBREGON, BRAR, OLIVER
is_lateral_inspection
false