Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 22, 2022, 05:11 AM
  • 08 0213_08 0212A_06212022_234634.mp4

Date
06/21/2022
W/O
957403
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00005
PipeID
P21320
Time
10:11 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10186
Sewer Name
08 EAST ROAD TRUNK
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_957403_TV08013_JUN2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
08 0213
Downstream MH
08 0212A
Dir. of Survey
Downstream
Length Surveyed
242.2 ft.
Total Length
242.2 ft.
Structural Index
4
Structural Quick
4131
Structural Rating
7
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
4
Overall Quick
Overall Rating
11
Pipe schematic from manhole 08 0213 to 08 0212A
MH: 08 0213MH: 08 0212Adownstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 02130 ft. MWM - Water Mark, 25 %of cross sectional area3.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start32.1 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"32.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish32.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start110 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"184.9 ft. RBL - Roots Ball Lateral, at 12 o'clock, 75 %184.9 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6", 6"238.2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish241.9 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK242.2 ft. AMH - Downstream Manhole, Survey Ends - 08 0212A

Observation photos (3)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    32.6 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Ball Lateral, at 12 o'clock, 75 %

    184.9 ft. - Roots Ball Lateral, at 12 o'clock, 75 %

Observations (13)

DistanceCodeObservation
0MWL
242.2AMH08 0212A
184.9RBL
3.6CM
0AMH08 0213
32.1TFC
241.9MGOCONNECTION AT MH 3 O'CLOCK
0MWM
238.2FM
32.6CM
32.6FM
184.9TF
110TFC

Properties (7)

additional_info
630074062122202
custom_field_three
MULTIPLE FRACTURE'S
custom_field_two
2
customer
1
datetime
2022-06-21T22:11:14-07:00
documentation
PROPIPE
is_lateral_inspection
false