- Date
- 06/21/2022
- W/O
- 957403
- Weather
- Dry
- Operator/Surveyor
- B.FUGATE
- Sewer ID
- Z00005
- PipeID
- P00090
- Time
- 11:36 PM
- Certificate
- U-508-7069
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K10186
- Sewer Name
- 08 EAST ROAD TRUNK
- City
- CARSON
- Loc. details
- Main Highway - Urban
- Location Code
- A
- Use of Sewer
- Sanitary Sewer
- District
- District 08
- Page No.
- 10
- Purpose
- Routine Assessment
- Project
- RFIR_WO_957403_TV08013_JUN2022
- Sewer Type
- Gravity
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 12 in.
- Width
- 12 in.
- Upstream MH
- 08 0220
- Downstream MH
- 08 0219
- Dir. of Survey
- Downstream
- Length Surveyed
- 162.5 ft.
- Total Length
- 162.5 ft.
- Structural Index
- 4
- Structural Quick
- 4100
- Structural Rating
- 4
- O&M Index
- 1
- O&M Quick
- 1100
- O&M Rating
- 1
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 5
Pipe schematic from manhole 08 0220 to 08 0219 Observation photos (3)

3.8 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

15.3 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

135.2 ft. - Roots Fine Joint, from 07 to 05 o'clock, within 8 inches of joint: YES