Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 9, 2022, 09:43 AM
  • H 0670_H 0669_05092022_040016.mp4

Date
05/09/2022
W/O
951829
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00941
PipeID
P11077
Time
2:43 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10092
Sewer Name
H JOINT OUTFALL H - UNIT 9B
City
PICO RIVERA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
03
Purpose
Routine Assessment
Project
RFIR_WO_951829_TV18175_MAY2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
25 in.
Width
25 in.
Upstream MH
H 0669
Downstream MH
H 0670
Dir. of Survey
Upstream
Length Surveyed
517.3 ft.
Total Length
517.3 ft.
Structural Index
3
Structural Quick
3S00
Structural Rating
306
O&M Index
2
O&M Quick
2E00
O&M Rating
64
Overall Index
3
Overall Quick
Overall Rating
370
Pipe schematic from manhole H 0669 to H 0670
MH: H 0669MH: H 0670upstream0 ft. MGO - General Observation - MOBILE MMS - 520.00'0 ft. AMH - Upstream Manhole, Survey Ends - H 06702.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish128.3 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Finish288.5 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Start515.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start517.3 ft. MWL - Water Level, 10 %of cross sectional area517.3 ft. MWM - Water Mark, 20 %of cross sectional area517.3 ft. AMH - Downstream Manhole, Survey Begins - H 0669

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Settled Other,  10 %of cross sectional area, at 06 o'clock,  , within 8 inches of joint: YES, Start

    228.8 ft. - Deposits Settled Other, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
2.1SAV
514.4SAV
517.3MGOMOBILE MMS - 520.00'
228.8DSZ
0MWL
0MWM
517.3AMHH 0670
389DSZ
0AMHH 0669

Properties (7)

additional_info
630074050922001
custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2022-05-09T02:43:41-07:00
documentation
PROPIPE
is_lateral_inspection
false