Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 6, 2022, 06:43 AM
  • H 0699_H 0698_05062022_010051.mp4

Date
05/05/2022
W/O
951829
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00941
PipeID
P11106
Time
11:43 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10091
Sewer Name
H JOINT OUTFALL H - UNIT 9B
City
WHITTIER
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
01
Purpose
Routine Assessment
Project
RFIR_WO_951829_TV18175_MAY2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
25 in.
Width
25 in.
Upstream MH
H 0698
Downstream MH
H 0699
Dir. of Survey
Upstream
Length Surveyed
680.7 ft.
Total Length
680.7 ft.
Structural Index
3
Structural Quick
3Z00
Structural Rating
405
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
405
Pipe schematic from manhole H 0698 to H 0699
MH: H 0698MH: H 0699upstream0 ft. AMH - Upstream Manhole, Survey Ends - H 06992.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish678.3 ft. MGO - General Observation - MAG COAT678.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start680.7 ft. AMH - Downstream Manhole, Survey Begins - H 0698680.7 ft. MWM - Water Mark, 20 %of cross sectional area680.7 ft. MWL - Water Level, 10 %of cross sectional area

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.4 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (7)

DistanceCodeObservation
678.6SAV
0AMHH 0698
0MWM
2.4MGOMAG COAT
0MWL
2.4SAV
680.7AMHH 0699

Properties (7)

additional_info
630074050522201
custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2022-05-05T23:43:44-07:00
documentation
PROPIPE
is_lateral_inspection
false