Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 10, 2022, 07:21 PM
  • H 0691_H 0690_06102022_134140.mp4

Date
06/10/2022
W/O
951829
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00941
PipeID
P11098
Time
12:21 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10167
Sewer Name
H JOINT OUTFALL H - UNIT 9B
City
WHITTIER
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
01
Purpose
Routine Assessment
Project
RFIR_WO_951829_TV18175_MAY2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
25 in.
Width
25 in.
Upstream MH
H 0691
Downstream MH
H 0690
Dir. of Survey
Downstream
Length Surveyed
816.5 ft.
Total Length
816.5 ft.
Structural Index
3
Structural Quick
3_00
Structural Rating
486
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
486
Pipe schematic from manhole H 0691 to H 0690
MH: H 0691MH: H 0690downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 06912.5 ft. MGO - General Observation - MAG COAT2.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start815.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish816.5 ft. MGO - General Observation - MOBILE MMS - 812.47'816.5 ft. AMH - Downstream Manhole, Survey Ends - H 0690

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.6 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
816.5MGOMOBILE MMS - 812.47'
0MWL
0MWM
815.1SAV
816.5AMHH 0690
2.6SAV
0AMHH 0691
2.5MGOMAG COAT

Properties (7)

additional_info
630074061022061
custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2022-06-10T12:21:36-07:00
documentation
PROPIPE
is_lateral_inspection
false