Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 13, 2022, 02:19 PM
  • H 0689_H 0688_06132022_083136.mp4

Date
06/13/2022
W/O
951829
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00941
PipeID
P11096
Time
7:19 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10168
Sewer Name
H JOINT OUTFALL H - UNIT 9B
City
PICO RIVERA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
01
Purpose
Routine Assessment
Project
RFIR_WO_951829_TV18175_MAY2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
25 in.
Width
25 in.
Upstream MH
H 0688
Downstream MH
H 0689
Dir. of Survey
Upstream
Length Surveyed
480.9 ft.
Total Length
480.9 ft.
Structural Index
3
Structural Quick
3R00
Structural Rating
288
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
288
Pipe schematic from manhole H 0688 to H 0689
MH: H 0688MH: H 0689upstream0 ft. MGO - General Observation - MOBILE MMS - 481.61'0 ft. AMH - Upstream Manhole, Survey Ends - H 06891.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish478.8 ft. MGO - General Observation - MAG COAT478.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start480.9 ft. MWL - Water Level, 5 %of cross sectional area480.9 ft. MWM - Water Mark, 20 %of cross sectional area480.9 ft. AMH - Downstream Manhole, Survey Begins - H 0688

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
479.7SAV
480.9MGOMOBILE MMS - 481.61'
2.1MGOMAG COAT
0MWL
0MWM
2.1SAV
480.9AMHH 0689
0AMHH 0688

Properties (7)

additional_info
630074061322061
custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2022-06-13T07:19:43-07:00
documentation
PROPIPE
is_lateral_inspection
false