Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 23, 2022, 05:59 AM
  • 18 0014_18 0013_06232022_001018.mp4

Date
06/22/2022
W/O
957002
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00713
PipeID
P13830
Time
10:59 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10204
Sewer Name
18 WALNUT WAY TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_957002_TV18059_JUN2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 0014
Downstream MH
18 0013
Dir. of Survey
Downstream
Length Surveyed
222.2 ft.
Total Length
222.2 ft.
Structural Index
3
Structural Quick
3H2H
Structural Rating
220
O&M Index
2
O&M Quick
2H00
O&M Rating
88
Overall Index
2
Overall Quick
Overall Rating
308
Pipe schematic from manhole 18 0014 to 18 0013
MH: 18 0014MH: 18 0013downstream0 ft. MGO - General Observation - ROACHES @ MH0 ft. AMH - Upstream Manhole, Survey Begins - 18 00140 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start47.5 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"66.1 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6" - OPEN101.8 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN121.3 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6" - OPEN147.3 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN151.7 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN212.8 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN219.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish219.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish220 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish222.1 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ABANDONED222.2 ft. AMH - Downstream Manhole, Survey Ends - 18 0013222.2 ft. MGO - General Observation - ROACHES @ MH

Observation photos (4)

  • General Observation - ROACHES @ MH

    0 ft. - General Observation - ROACHES @ MH

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - ROACHES @ MH

    222.2 ft. - General Observation - ROACHES @ MH

Observations (20)

DistanceCodeObservation
219.5DAGS
101.8TBOPEN
212.8TBOPEN
0MGOROACHES @ MH
151.7TBOPEN
147.3TBOPEN
2DAGS
66.1TBOPEN
0AMH18 0014
2SAP
0MWM
2SSS
47.5TBA
222.1MGOCONN @ MH 9 O'CLOCK/ABANDONED
220SSS
219.5SAP
222.2AMH18 0013
0MWL
222.2MGOROACHES @ MH
121.3TBOPEN

Properties (7)

additional_info
630098062222201
custom_field_three
PROJECTING AGGREGATE
custom_field_two
3
customer
1
datetime
2022-06-22T22:59:59-07:00
documentation
PRO PIPE
is_lateral_inspection
false