Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 8, 2022, 06:31 AM
  • 08 0229_08 0228_07072022_235047.mp4

Date
07/07/2022
W/O
962037
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00005
PipeID
P00103
Time
11:31 PM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9974
Sewer Name
08 EAST ROAD TRUNK
City
TORRANCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_962037_TV08112_JUL2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
12 in.
Upstream MH
08 0229
Downstream MH
08 0228
Dir. of Survey
Downstream
Length Surveyed
351.1 ft.
Total Length
351.1 ft.
Structural Index
3
Structural Quick
4F3F
Structural Rating
241
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
241
Pipe schematic from manhole 08 0229 to 08 0228
MH: 08 0229MH: 08 0228downstream0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK CAPPED0 ft. AMH - Upstream Manhole, Survey Begins - 08 02290 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start98.6 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 8"180.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish180.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start193.6 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6"274.7 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 8"325.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 8"348.2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish351.1 ft. AMH - Downstream Manhole, Survey Ends - 08 0228351.1 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK CAPPED

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    180.6 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
348.2FM
98.6TFA
351.1AMH08 0228
4CM
274.7TF
180.6CM
193.6TF
0MGOCONNECTION AT MH 9 O'CLOCK CAPPED
0AMH08 0229
180.6FM
325.3TFC
0MWM
351.1MGOCONNECTION AT MH 9 O'CLOCK CAPPED
0MWL

Properties (7)

additional_info
630063070722201
custom_field_three
FRACTURES
custom_field_two
2
customer
1
datetime
2022-07-07T23:31:51-07:00
documentation
PRO PIPE
is_lateral_inspection
false