Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 8, 2022, 06:52 AM
  • 08 0228_08 0227_07082022_000019.mp4

Date
07/07/2022
W/O
962037
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00005
PipeID
P00102
Time
11:52 PM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9974
Sewer Name
08 EAST ROAD TRUNK
City
TORRANCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_962037_TV08112_JUL2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
12 in.
Upstream MH
08 0228
Downstream MH
08 0227
Dir. of Survey
Downstream
Length Surveyed
91.2 ft.
Total Length
91.2 ft.
Structural Index
3
Structural Quick
433A
Structural Rating
48
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
52
Pipe schematic from manhole 08 0228 to 08 0227
MH: 08 0228MH: 08 0227downstream0 ft. AMH - Upstream Manhole, Survey Begins - 08 02280 ft. MWL - Water Level, 30 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK CAPPED0 ft. MWM - Water Mark, 50 %of cross sectional area13.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start35.3 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 8"73.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start73.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish88.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish91.2 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK91.2 ft. AMH - Downstream Manhole, Survey Ends - 08 0227

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    13.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    73.4 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
73.4FM
73.4CM
0AMH08 0228
0MWL
0MGOCONNECTION AT MH 9 O'CLOCK CAPPED
35.3TF
91.2MGOCONNECTION AT MH 3 O'CLOCK
91.2AMH08 0227
0MWM
13.5CM
88.4FM

Properties (7)

additional_info
630063070722201
custom_field_three
FRACTURES
custom_field_two
2
customer
1
datetime
2022-07-07T23:52:07-07:00
documentation
PRO PIPE
is_lateral_inspection
false