Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 8, 2022, 07:02 AM
  • 08 0227_08 0226_07082022_001346.mp4

Date
07/08/2022
W/O
962037
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00005
PipeID
P00101
Time
12:02 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9974
Sewer Name
08 EAST ROAD TRUNK
City
TORRANCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_962037_TV08112_JUL2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
12 in.
Upstream MH
08 0227
Downstream MH
08 0226
Dir. of Survey
Downstream
Length Surveyed
135.4 ft.
Total Length
135.4 ft.
Structural Index
3
Structural Quick
3D00
Structural Rating
75
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
79
Pipe schematic from manhole 08 0227 to 08 0226
MH: 08 0227MH: 08 0226downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 02270 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWL - Water Level, 30 %of cross sectional area6.5 ft. FS - Fracture Spiral, from 08 to 04 o'clock, within 8 inches of joint: YES, Start43.5 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 8"52.8 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 6"112.4 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 8"133 ft. FS - Fracture Spiral, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish135.4 ft. AMH - Downstream Manhole, Survey Ends - 08 0226135.4 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK

Observation photos (2)

  • Fracture Spiral, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.5 ft. - Fracture Spiral, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 6"

    52.8 ft. - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 6"

Observations (11)

DistanceCodeObservation
43.5TFC
112.4TF
6.5FS
52.8TB
135.4AMH08 0226
0MWM
133FS
0AMH08 0227
0MGOCONNECTION AT MH 3 O'CLOCK
135.4MGOCONNECTION AT MH 3 O'CLOCK
0MWL

Properties (7)

additional_info
630063070722201
custom_field_three
FRACTURES
custom_field_two
2
customer
1
datetime
2022-07-08T00:02:22-07:00
documentation
PRO PIPE
is_lateral_inspection
false