Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 8, 2022, 07:16 AM
  • 08 0226_08 0225_07082022_002553.mp4

Date
07/08/2022
W/O
962037
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00005
PipeID
P00100
Time
12:16 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9974
Sewer Name
08 EAST ROAD TRUNK
City
TORRANCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_962037_TV08112_JUL2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
12 in.
Upstream MH
08 0226
Downstream MH
08 0225
Dir. of Survey
Downstream
Length Surveyed
123.2 ft.
Total Length
123.2 ft.
Structural Index
3
Structural Quick
3D00
Structural Rating
72
O&M Index
3
O&M Quick
4122
O&M Rating
8
Overall Index
3
Overall Quick
Overall Rating
80
Pipe schematic from manhole 08 0226 to 08 0225
MH: 08 0226MH: 08 0225downstream0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 02263 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start52 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 8"111 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start123 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Finish123 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish123.2 ft. MGO - General Observation - CONNECTION AT MH BOTH 3 & 9 O'CLOCK123.2 ft. AMH - Downstream Manhole, Survey Ends - 08 0225

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock,  , within 8 inches of joint: YES, Start

    111 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
0MGOCONNECTION AT MH 3 O'CLOCK
123DAE
111DAE
52TF
123.2MGOCONNECTION AT MH BOTH 3 & 9 O'CLOCK
123CM
0MWM
0MWL
0AMH08 0226
123.2AMH08 0225
3CM

Properties (7)

additional_info
630063070722201
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2022-07-08T00:16:27-07:00
documentation
PRO PIPE
is_lateral_inspection
false