Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 15, 2022, 05:33 AM
  • 08 0224_08 0223A_07142022_224841.mp4

Date
07/14/2022
W/O
962037
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00005
PipeID
P00098
Time
10:33 PM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9982
Sewer Name
08 EAST ROAD TRUNK
City
W CARSON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_962037_TV08112_JUL2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
08 0224
Downstream MH
08 0223A
Dir. of Survey
Downstream
Length Surveyed
280.4 ft.
Total Length
280.4 ft.
Structural Index
3
Structural Quick
3300
Structural Rating
9
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
13
Pipe schematic from manhole 08 0224 to 08 0223A
MH: 08 0224MH: 08 0223Adownstream0 ft. AMH - Upstream Manhole, Survey Begins - 08 02240 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK47.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"89.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES98.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"105.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES112.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start149.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - HOLE INSIDE197.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"248.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"277.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish280.4 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK280.4 ft. AMH - Downstream Manhole, Survey Ends - 08 0223A

Observation photos (4)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    89.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    105.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    112.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - HOLE INSIDE

    149.4 ft. - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - HOLE INSIDE

Observations (15)

DistanceCodeObservation
105.2CM
248.2TFC
197.3TFC
47.2TFC
280.4MGOCONNECTION AT MH 9 O'CLOCK
0AMH08 0224
112.2CM
0MWL
277.9CM
149.4TFHOLE INSIDE
0MWM
0MGOCONNECTION AT MH 3 O'CLOCK
98.4TFC
280.4AMH08 0223A
89.3CM

Properties (7)

additional_info
630074071422202
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2022-07-14T22:33:09-07:00
documentation
PRO PIPE
is_lateral_inspection
false