Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 8, 2022, 09:13 AM
  • 08 0218_08 0217_07082022_023052.mp4

Date
07/08/2022
W/O
962037
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00005
PipeID
P00088
Time
2:13 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9974
Sewer Name
08 EAST ROAD TRUNK
City
TORRANCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_962037_TV08112_JUL2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
08 0218
Downstream MH
08 0217
Dir. of Survey
Downstream
Length Surveyed
420.6 ft.
Total Length
420.6 ft.
Structural Index
3
Structural Quick
4E3I
Structural Rating
276
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
282
Pipe schematic from manhole 08 0218 to 08 0217
MH: 08 0218MH: 08 0217downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 02180 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWL - Water Level, 10 %of cross sectional area4.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start34.4 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 8"104.6 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 12 to 12 o'clock, , within 8 inches of joint: YES105.8 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 8"181.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 8"256.6 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 8"266.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish266.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start332.1 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 8"407.6 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"414.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish420.6 ft. MGO - General Observation - CONNECTION AT MH BOTH 3 & 9 O'CLOCK CAPPED420.6 ft. AMH - Downstream Manhole, Survey Ends - 08 0217

Observation photos (3)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 10 %of cross sectional area, from 12 to 12 o'clock,  , within 8 inches of joint: YES

    104.6 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 12 to 12 o'clock, , within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    266.6 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (17)

DistanceCodeObservation
105.8TFA
414.7FM
407.6TFC
181.3TFC
0MWM
0AMH08 0218
420.6MGOCONNECTION AT MH BOTH 3 & 9 O'CLOCK CAPPED
266.6CM
266.6FM
256.6TFA
420.6AMH08 0217
104.6DAGS
4.5CM
34.4TFC
0MGOCONNECTION AT MH 9 O'CLOCK
332.1TFC
0MWL

Properties (7)

additional_info
630063070722201
custom_field_three
FRACTURES
custom_field_two
2
customer
1
datetime
2022-07-08T02:13:23-07:00
documentation
PRO PIPE
is_lateral_inspection
false