Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 8, 2022, 09:31 AM
  • 08 0217_08 0216_07082022_024420.mp4

Date
07/08/2022
W/O
962037
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00005
PipeID
P00087
Time
2:31 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9974
Sewer Name
08 EAST ROAD TRUNK
City
TORRANCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_962037_TV08112_JUL2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
15 in.
Upstream MH
08 0217
Downstream MH
08 0216
Dir. of Survey
Downstream
Length Surveyed
349.8 ft.
Total Length
349.8 ft.
Structural Index
4
Structural Quick
4L35
Structural Rating
269
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
4
Overall Quick
Overall Rating
273
Pipe schematic from manhole 08 0217 to 08 0216
MH: 08 0217MH: 08 0216downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 02170 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH BOTH 3 & 9 O'CLOCK CAPPED4.2 ft. CS - Crack Spiral, from 08 to 04 o'clock, within 8 inches of joint: YES5.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start29.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish29.9 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start347.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish349.8 ft. AMH - Downstream Manhole, Survey Ends - 08 0216349.8 ft. MGO - General Observation - CONNECTION AT MH BOTH 3 & 9 O'CLOCK CAPPED

Observation photos (3)

  • Crack Spiral, from 08 to 04 o'clock, within 8 inches of joint: YES

    4.2 ft. - Crack Spiral, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    29.9 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
0MWM
349.8AMH08 0216
347.3FM
4.2CS
0AMH08 0217
29.9CM
0MWL
349.8MGOCONNECTION AT MH BOTH 3 & 9 O'CLOCK CAPPED
29.9FM
5.6CM
0MGOCONNECTION AT MH BOTH 3 & 9 O'CLOCK CAPPED

Properties (7)

additional_info
630063070722201
custom_field_three
FRACTURES
custom_field_two
2
customer
1
datetime
2022-07-08T02:31:29-07:00
documentation
PRO PIPE
is_lateral_inspection
false