Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 15, 2022, 07:17 AM
  • 08 0214_08 0213_07152022_003512.mp4

Date
07/15/2022
W/O
962037
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00005
PipeID
P00084
Time
12:17 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9982
Sewer Name
08 EAST ROAD TRUNK
City
W CARSON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_962037_TV08112_JUL2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
15 in.
Upstream MH
08 0214
Downstream MH
08 0213
Dir. of Survey
Downstream
Length Surveyed
350.5 ft.
Total Length
350.5 ft.
Structural Index
4
Structural Quick
4100
Structural Rating
4
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
4
Overall Quick
Overall Rating
8
Pipe schematic from manhole 08 0214 to 08 0213
MH: 08 0214MH: 08 0213downstream0 ft. AMH - Upstream Manhole, Survey Begins - 08 02140 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area5.1 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"6.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start79.3 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6"153.6 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"232.4 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6"306.7 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"350.5 ft. AMH - Downstream Manhole, Survey Ends - 08 0213350.5 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (1)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.1 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
5.1TFC
350.5AMH08 0213
306.7TFC
153.6TFC
232.4TF
0AMH08 0214
79.3TF
350.5FM
0MWM
0MWL
6.1FM

Properties (7)

additional_info
630074071422202
custom_field_three
FRACTURES
custom_field_two
3
customer
1
datetime
2022-07-15T00:17:29-07:00
documentation
PRO PIPE
is_lateral_inspection
false