Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 27, 2022, 08:17 AM
  • H 0333_H 0332_07272022_012654.mp4

Date
07/27/2022
W/O
961907
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00175
PipeID
P10783
Time
1:17 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9992
Sewer Name
H JOINT OUTFALL H - UNIT 4
City
PICO RIVERA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
19
Purpose
Routine Assessment
Project
RFIR_WO_961907_TV02325_JUL2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
57 in.
Width
57 in.
Upstream MH
H 0333
Downstream MH
H 0332
Dir. of Survey
Downstream
Length Surveyed
280.5 ft.
Total Length
280.5 ft.
Structural Index
3
Structural Quick
3J00
Structural Rating
168
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
172
Pipe schematic from manhole H 0333 to H 0332
MH: H 0333MH: H 0332downstream0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 03332 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start280.5 ft. MGO - General Observation - PIPE RUNNING THROUGH MANHOLE280.5 ft. AMH - Downstream Manhole, Survey Ends - H 0332280.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - PIPE RUNNING THROUGH MANHOLE

    280.5 ft. - General Observation - PIPE RUNNING THROUGH MANHOLE

Observations (7)

DistanceCodeObservation
0MWL
280.5MGOPIPE RUNNING THROUGH MANHOLE
280.5AMHH 0332
0MWM
2SAP
0AMHH 0333
280.5SAP

Properties (7)

additional_info
630074072622202
custom_field_three
AGGREGATE PROJECTING
custom_field_two
2
customer
1
datetime
2022-07-27T01:17:38-07:00
documentation
PRO PIPE
is_lateral_inspection
false